Simulating the GB power system frequency during underfrequency events 2018-19
preprint
OA: closed
Abstract
AbstractLightning hit a transmission powerline outside London, England on 9 August 2019. There followed a loss of power from a cascade of generator outages that exceeded contingency reserves, leading to an exceptional fall in grid frequency causing widespread transport disruptions and the disconnection of over 1m households. Simulating such events typically involves a system of differential equations representing the overall generation and load present at the time. The standard model based on the swing equation assumes unlimited capacity in aggregated resources, as well as the availability of these services for the duration of the frequency excursion. In simulating the effect of outages on the GB Grid frequency on 2019/8/9, the effect of limiting these services to the capacity of resources engaged during the event is examined. It is shown that by taking these refinements into account the timing and extent of the frequency nadir can be successfully estimated. Insight is gained into the responses of various characteristics of the grid and how they interact with unplanned generation imbalances. Using this adapted model, further events on the GB grid are examined to validate the influence of these features. With the effectiveness of the model validated, novel mitigating measures to preserve the stability of a low-inertia grid can be evaluated.
My notes (saved in your browser only)
Citation neighborhood (no data yet)
We don't have any in-corpus citations linked to this paper yet. The paper's references may be in our DB but unresolved to ``paper_id`` (resolution happens at ingest when the cited DOI matches a row we already have). Run the cross-source citation reconcile pass to retry.
Source provenance
- europepmc
- last seen: 2026-05-19T01:45:01.086888+00:00