In-Situ Comparison between the Energy Performance of an In-Slab Gas Heating System and a Split System Air Conditioning in Classrooms

preprint OA: closed
View at publisher

Abstract

Sub-metered energy use of an in-slab gas hydronic heating system and a newly installed split system air conditioner in thermodynamically-equivalent classrooms are compared during unoccupied (with artificially imposed internal heat gains) and occupied periods. A preliminary comparison is also undertaken to quantify the heating penalty for the existing gas-fuelled hydronic heating systems when windows remain open (e.g. to comply with COVID-19 guidelines in schools) against the energy needed for heating by the same system in a control classroom with windows closed.The performance evaluation of the heating systems during three unoccupied days where internal heat gains were artificially imposed demonstrated that the gas hydronic system used 41.5 kWh while the AC split system used 7.2 kWh, with the AC split system being able to maintain the internal conditions above the set point by operating for approximately one third of the time the hydronic system was operating.Occupied tests confirmed the observations of the unoccupied tests of equivalent operation. Over a period of 2 occupied winter weeks, the in-slab gas hydronic heating system used 274.6 kWh and operated for 35¼ hrs, while the AC split system used 34.7 kWh and operated for 22¼ hrs, albeit on some occasions the occupants in the AC split system’s classroom chose not to turn on the system. After selecting days from this occupied period when both systems were used for long periods, it was observed that the AC split system used approximately 4 to 7 times less energy than the in-slab gas hydronic system.Finally, from the preliminary test, the parallel measurements also confirmed that the additional ventilation in schools through opening of windows increases the energy use of the hydronic heating system; 66.8 kWh were measured for heating needs over a period of 3-days as opposed to 25 kWh for the windows open and closed cases respectively. These precise values are, however dependent on the season and building type.

My notes (saved in your browser only)

Citation neighborhood (no data yet)

We don't have any in-corpus citations linked to this paper yet. The paper's references may be in our DB but unresolved to ``paper_id`` (resolution happens at ingest when the cited DOI matches a row we already have). Run the cross-source citation reconcile pass to retry.

Source provenance

europepmc
last seen: 2026-05-19T01:45:01.086888+00:00